What is the single channel configuration?

Usually, the CAN-ID for CSM measurement modules is defined for a group of channels. Often valid for the entire module. This then occupies a consecutive range of CAN identifiers.
For some measurement modules, however, the CAN identifier and transmission rate can also be specified per channel. CAN identifiers can be defined channel by channel individually. However, the format (11/29 bit) must correspond to the CAN bus definition.

The option to define CAN identifier and transmission rate per channel is activated in the "Device Configuration" dialog or in the "Device List" view.

Restrictions for single channel configuration:

  • If the Configuration per channel option is activated, the info message cannot be activated for some modules.
  • The measuring module generates a higher bus load if the channels transmit in separate CAN messages.
  • The option to define CAN identifier and transmission rate per channel is not supported by all analyzer modules / firmware versions.
  • The ID NULL switches off the respective channel. No CAN message is sent.